【Origin Pic】 |
UPS power system EA600 1-2kVA
Power range:10kVA~90kVA
Application field: EA-D type fire emergency lighting special emergency |
EA series emergency power supply system is to solve the power supply problem of emergency lighting, emergency lighting, industrial facilities and other primary load backup power supply equipment as its main goal, providing an emergency power supply system that meets fire protection regulations, user requirements, and has an independent loop. . The system can provide emergency power supply in an emergency state to solve the problem of lighting power or only one mains lack of a second power supply, or replace the generator set to form a second power supply, or use it in occasions where a third power supply is needed. The products are mainly divided into three categories: EA-D type special emergency power supply for fire emergency lamps, FEPS type emergency power supply for fire equipment, EPSS type backup emergency power supply.
10kVA~90kVA
Application field:EA-D type special emergency power supply for fire emergency lighting: suitable for emergency power supply equipment suitable for fire emergency lighting, emergency lighting, evacuation instructions, and various first-class loads.
Has been certified by a third-party authority:Tail certification, energy saving certification, CE certification, seismic certification.
Has been certified by a third-party authority:
Fire certification
★Technical characteristics of EPSØThe application of advanced DDC technology, DSP technology and special IC makes the product have excellent performance
ØWith fire protection linkage, standard RS485 communication monitoring interface
ØIsolation transformer output, with the advantages of voltage stabilization, frequency stabilization, low noise and high reliability
ØIntuitive LCD display, can store 1000 records, clear at a glance
ØDual power supply automatic switching, high reliability
ØDry contact interface, using passive nodes to monitor the status of EPS
ØHand/automatic annual and monthly inspection function, always detect and protect the battery
ØAutomatic switching, unattended
Ø5 modes of continuous output (default), direct output, emergency output, controlled output, and non-continuous output are optional, and all can be selected
★EPS technical parameters3.1 EA-D Special emergency power supply for fire emergency lighting
Item\capacity | 10kVA |
15kVA |
20kVA |
30kVA |
40kVA |
50kVA |
60kVA |
80kVA |
90kVA |
|
Enter |
DC voltage |
492VDC |
||||||||
Mains voltage |
380VAC (+15%, -20%) |
|||||||||
Mains frequency |
50HZ±5% |
|||||||||
Output |
Output voltage |
Normal status: consistent with mains power |
||||||||
Emergency status: 380 V±3% |
||||||||||
Output frequency |
Normal status: consistent with mains power |
|||||||||
Emergency status: 50±0.1Hz |
||||||||||
Number of output channels |
1 Road |
|||||||||
Output method |
Continuous output |
|||||||||
Efficiency (amount definitely negative |
≥98% (main power), ≥88% (emergency) |
|||||||||
Output waveform |
Sine wave |
|||||||||
Switching time |
≤100 milliseconds |
|||||||||
Overload capability |
120% long-term operation, 125% one-minute protection, 150% one-second protection |
|||||||||
Emergency power supply time |
90 minutes |
|||||||||
Protection function |
Over temperature protection, inverter over and under voltage protection, battery under voltage protection, overload protection, BUS over voltage, output short circuit protection |
|||||||||
Status display |
LCD Chinese character information display+LED operation status indication |
|||||||||
Communication function |
RS485 |
|||||||||
Control function |
Hand/auto function, forced start function, automatic monthly/annual inspection function, analog main power failure function, reset function, elimination |
|||||||||
Adapt to load |
Emergency lighting type lamp load |
|||||||||
Noise |
Normal state: ≤45dB |
|||||||||
Ambient temperature |
-10 degree-40 degree |
|||||||||
Relative humidity |
20%-90% |
|||||||||
Altitude |
≤1000m (for each additional 100 m power decrease 1%) |
|||||||||
Protection level |
IP41 |
|||||||||
Battery location |
Separate external battery cabinet |
Note: Specifications are subject to change without notice. The pictures are provided for reference, and the actual product shall prevail.