Dongguan Shengrong Communication Engineering Co., Ltd. Shengrong

UPS INDUSTRIAL POWER ONE-STOP SOURCE MANUFACTURER WHOLESALE

4dhcpmingchen

【Origin Pic】
UPS power system EA600 1-2kVA
Power range:10kVA~90kVA
Application field: EA-D type fire emergency lighting special emergency
★Basic introduction to EPS

EA series emergency power supply system is to solve the power supply problem of emergency lighting, emergency lighting, industrial facilities and other primary load backup power supply equipment as its main goal, providing an emergency power supply system that meets fire protection regulations, user requirements, and has an independent loop. . The system can provide emergency power supply in an emergency state to solve the problem of lighting power or only one mains lack of a second power supply, or replace the generator set to form a second power supply, or use it in occasions where a third power supply is needed. The products are mainly divided into three categories: EA-D type special emergency power supply for fire emergency lamps, FEPS type emergency power supply for fire equipment, EPSS type backup emergency power supply.

Power range:

10kVA~90kVA

Application field:

EA-D type special emergency power supply for fire emergency lighting: suitable for emergency power supply equipment suitable for fire emergency lighting, emergency lighting, evacuation instructions, and various first-class loads.

Has been certified by a third-party authority:

Tail certification, energy saving certification, CE certification, seismic certification.

Has been certified by a third-party authority:

Fire certification

★Technical characteristics of EPS

ØThe application of advanced DDC technology, DSP technology and special IC makes the product have excellent performance

ØWith fire protection linkage, standard RS485 communication monitoring interface

ØIsolation transformer output, with the advantages of voltage stabilization, frequency stabilization, low noise and high reliability

ØIntuitive LCD display, can store 1000 records, clear at a glance

ØDual power supply automatic switching, high reliability

ØDry contact interface, using passive nodes to monitor the status of EPS

ØHand/automatic annual and monthly inspection function, always detect and protect the battery

ØAutomatic switching, unattended

Ø5 modes of continuous output (default), direct output, emergency output, controlled output, and non-continuous output are optional, and all can be selected

★EPS technical parameters

3.1  EA-D Special emergency power supply for fire emergency lighting



Item\capacity

10kVA

15kVA

20kVA

30kVA

40kVA

50kVA

60kVA

80kVA

90kVA

 

Enter

DC voltage

492VDC

Mains voltage

380VAC (+15%, -20%)

Mains frequency

50HZ±5%

 

 

 

Output

 

Output voltage

Normal status: consistent with mains power

Emergency status: 380 V±3%

 

Output frequency

Normal status: consistent with mains power

Emergency status: 50±0.1Hz

Number of output channels

1 Road

Output method

Continuous output

Efficiency (amount definitely negative 
Download)

≥98% (main power), ≥88% (emergency)

Output waveform

Sine wave

Switching time

≤100 milliseconds

Overload capability

120% long-term operation, 125% one-minute protection, 150% one-second protection

Emergency power supply time

90 minutes

Protection function

Over temperature protection, inverter over and under voltage protection, battery under voltage protection, overload protection, BUS over voltage, output short circuit protection

Status display

LCD Chinese character information display+LED operation status indication

Communication function

RS485

Control function

Hand/auto function, forced start function, automatic monthly/annual inspection function, analog main power failure function, reset function, elimination
Anti-linkage function

Adapt to load

Emergency lighting type lamp load

Noise

Normal state: ≤45dB
Emergency state: ≤65dB

Ambient temperature

-10 degree-40 degree

Relative humidity

20%-90%

Altitude

≤1000m (for each additional 100 m power decrease 1%)

Protection level

IP41

Battery location

Separate external battery cabinet

Note: Specifications are subject to change without notice. The pictures are provided for reference, and the actual product shall prevail.