Dongguan Shengrong Communication Engineering Co., Ltd. Shengrong

UPS INDUSTRIAL POWER ONE-STOP SOURCE MANUFACTURER WHOLESALE

4dhcpmingchen

【Origin Pic】
Online outdoor machine 1KVA-3KVA

Power range:1kVA – 3kVA

Main components: Outdoor dedicated UPS, battery pack, outdoor integrated 


★ Basic introduction to online outdoor UPS

Online outdoor UPS is a company specializes in providing users with pure uninterrupted AC power equipment for outdoor communication and network equipment. It is mainly used for outdoor communication and network equipment, which are usually used in urban corners, remote suburbs, mountainous areas, etc. Designed for the power supply environment, adopting a series of designs such as high temperature resistance, severe cold resistance, salt fog resistance, corrosion resistance, dust resistance, waterproofing, lightning protection, etc., with a wide input voltage range, a wide input frequency range, and a pure, stable, and reliable output waveform. Advantages, it completely solves the interference of the harsh power supply environment on network communication equipment, power supply interruption and other phenomena, and is widely used in outdoor communication base stations in the fields of communication, radio and television, and aviation.

Power range:

1kVA – 3kVA

Main components:

Outdoor dedicated UPS, battery pack, outdoor integrated cabinet with power distribution

Application field:

Outdoor communication base stations in the fields of communications, radio and television, aviation, etc.

★Technical characteristics of online outdoor UPS

1) Strong environmental adaptability 1) Strong environmental adaptability

The outdoor integrated cabinet adopts the IP55 protection level, has the functions of dustproof and waterproof, and can meet the harsh outdoor environment.

Anti-high and low temperature design, the cabinet adopts design measures such as shading, heat insulation, temperature compensation, and strive to maintain the temperature in the cabinet to ensure the normal operation of the host and battery, and can adapt to normal operation under the environment of -20℃~+45℃.

With lightning protection and other surge protection, the system is equipped with a 1.2KV/10KA pluggable lightning protection device to effectively prevent lightning damage to the equipment.

2) Strong grid adaptability

Ultra-wide input voltage range and frequency range, the maximum input range of the mains can reach 110Vac~300Vac, and the frequency can reach 40Hz-60Hz, which is fully adapted to the harsh grid environment.

The input is equipped with a high-voltage protection circuit, which can withstand high voltage beyond the input voltage range for a long time without damage.

The online double conversion structure can completely eliminate the interference of the power grid spikes, noise, harmonics and other communication equipment.

3) Advanced technology and powerful functions

Adopt advanced digital microprocessor control, simplify the control circuit, and improve the stability and reliability of the system.

Using power factor correction technology (PFC), high input power factor, reducing UPS's harmonic pollution to other equipment, improving the utilization rate of the power grid, and reducing UPS operating costs. It is a cost-effective green and environmentally friendly power supply.

Digital control technology makes the efficiency of the whole machine greater than 90%, reduces the loss of UPS itself, and reduces the temperature inside the cabinet.

Double conversion structure working mode, to ensure zero switching between mains and battery power supply, and to ensure that the load is uninterrupted.

It can realize the unattended function. After the battery discharge protection, when the utility power is restored and normal, the UPS will automatically start to supply power to the load.

The system is equipped with a fault diagnosis function, which can quickly determine the cause of UPS failure and locate the fault location of the UPS through the combination of LED display, making UPS maintenance convenient and fast.

It has a cold start function. When there is no mains power, the battery pack can be used to start the UPS directly to meet the emergency needs of users.

The system is equipped with RS232 and dry contact communication interfaces to facilitate access to the transmission system monitoring, and realize unified monitoring and management with other equipment.

4) A variety of options, add on demand

A variety of optional installation accessories are provided to meet various installation requirements such as pole holding, wall hanging, and floor.

But it must be considered according to the actual situation of the customer. The usual installation method is floor-mounted installation. The bearing capacity of the pole and the wall must be considered.

Provide the optional function of secondary power-off (optional), when the battery is powered, the secondary load can be disconnected on time as needed to ensure the backup power supply time of the primary load, and a secondary power-off dry contact can be provided Signal.

SNMP can be installed to realize remote network monitoring and management, and provide real-time UPS data and information.

SNMP card enables multiple computers to monitor one UPS or one computer in the control room to monitor all UPSs (because outdoor machines are distributed in relatively remote places, to check the working status of UPS in time for management.

You only need to install the dry contact card (optional) to use the UPS monitoring function of the dry contact card to monitor and manage the power supply.

Dry node alarms, using relay output form.

Each alarm function: UPS failure, mains failure, low battery


Parameter definition of UPS dry node alarm output

UPS fault alarm:

When UPS mains voltage is too high or too low; output voltage is too high or too low; overload; short circuit, inverter temperature is too high; battery low; battery overcharge; UPS internal hardware failure, etc., UPS will A fault alarm has occurred.

Mains power failure:

When the load is less than 70%, and the mains voltage is ≤115±5V or ≥300±5V, the mains power is abnormal;

When the load is ≥70%, the mains voltage is ≤165±5V or ≥300±5V, the mains power is abnormal;

When the mains input frequency is less than or equal to 46HZ or ≥54HZ, the mains power is faulty.

3. Low battery warning:

When the battery discharge voltage is less than or equal to 11VDC (single battery), the battery low voltage alarm.

4. Access control alarm:

When the door is opened, the access control alarms.

Remarks:

The alarm output mode is the relay output type. When a fault alarms, the corresponding alarm point is short-circuited with the common point, and when it is normal, the corresponding alarm point and the common point are open.

★Technical parameters of online outdoor UPS


Type    number

EA1K-HW

EA2K-HW

EA3K-HW

Rated capacity

1kVA

2kVA

3kVA

Enter metrics

Enter the number of phases

Single-phase three-wire (1Φ+N+PE)

Enter the rated voltage

220Vac

Input voltage variable range

110~140VAC (half load) 140~300VAC (full load)

Enter the frequency variation range

45Hz~55Hz

Enter the power factor

≥0.99

Bypass input voltage range

186~252Vac

Battery voltage

24VDC

48VDC

72VDC

Output index

Number of output phases

Single-phase three-wire (1Φ+N+PE)

Output rated voltage

220Vac

Output voltage regulation accuracy

±2%

Output frequency accuracy

Mains mode: track bypass input in synchronization state; battery mode: 50Hz/60Hz±0.05Hz

Output power factor

0.8

Output waveform distortion degree

≤2% (linear load), ≤5% (non-linear load)

Output current crest factor

3:1

Inverter overload capacity

108<load≤125%, turn to bypass after 10min operation; when 125<load≤150% rated load, turn after 30 seconds Bypass; load>150%, 300ms to bypass

System metrics

System efficiency

≥90%

Switching time

≤0ms

Protection function

Output short circuit protection, output overload protection, over temperature protection, battery low voltage protection, output over and under voltage protection, fan failure protection, etc.

Communication interface

Standard configuration: RS232, dry contact;  Optional configuration: SNMP card, RS485, temperature compensation, etc.

Power Distribution Unit

Mains/battery input and output MCBs, input/output wiring blocks, output sockets, maintenance bypass switches, lightning protection devices, etc.

p>

display    show

LED

Working environment

Operating temperature

-20℃~45℃

Storage temperature

-45℃~+70℃

Relative humidity

0%-95% (no condensation)

Altitude

Altitude ≤1000m, over 1000m, derating 1% for every 100m rise

Protection level

IP55

Noise    Sound

<50dB (1 meter away from the device)

Other features

Host size         (W×D×H) mm

600×334×990

600×434×1110

Built-in battery space

12V2 section 65~100AH ​​

12V4 section 65~100AH ​​

12V6 section 65~100AH ​​

yan   color

Computer white

Note: Specifications are subject to change without notice. The pictures are provided for reference, and the actual product shall prevail.

★The appearance of the front panel of the online outdoor UPS

★Online outdoor UPS internal power distribution diagram