【Origin Pic】 |
Rectifier cabinet emergency power supply EPS-500KVA
★Power range:10kVA~100kVA
EA-D type special emergency power supply for fire emergency |
EA series emergency power supply system is to solve the power supply problem of emergency lighting, emergency lighting, industrial facilities and other primary load backup power supply equipment as its main goal, providing an emergency power supply system that meets fire protection regulations, user requirements, and has an independent loop. . The system can provide emergency power supply in an emergency state to solve the problem of lighting power or only one mains lack of a second power supply, or replace the generator set to form a second power supply, or use it in occasions where a third power supply is needed. The products are mainly divided into three categories: EA-D type special emergency power supply for fire emergency lamps, FEPS type emergency power supply for fire equipment, EPSS type backup emergency power supply.
10kVA~100kVA
EA-D type special emergency power supply for fire emergency lighting: suitable for emergency power supply equipment suitable for fire emergency lighting, emergency lighting, evacuation instructions, and various first-class loads.
FEPS emergency power supply for fire-fighting equipment: suitable for emergency power supply equipment suitable for fire emergency lighting, emergency lighting, evacuation instructions, and various first-class loads.
EPSS type backup emergency power supply: suitable for various lighting systems, indicating systems, widely used in various water pumps, spray pumps, living pumps, exhaust fans, positive pressure fans in buildings, as well as metallurgy, textile, petrochemical, Mines, squares, stations, parks, stadiums, convention and exhibition centers and other important places provide emergency power supply for primary load power supply;
Fire certification
★Technical characteristics of EPSØThe application of advanced DDC technology, DSP technology and special IC makes the product have excellent performance
ØWith fire protection linkage, standard RS485 communication monitoring interface
ØIsolation transformer output, with the advantages of voltage stabilization, frequency stabilization, low noise and high reliability
ØIntuitive LCD display, can store 1000 records, clear at a glance
ØDual power supply automatic switching, high reliability
ØDry contact interface, using passive nodes to monitor the status of EPS
ØHand/automatic annual and monthly inspection function, always detect and protect the battery
ØAutomatic switching, unattended
Ø5 modes of continuous output (default), direct output, emergency output, controlled output, and non-continuous output are optional, and all can be selected
★EPS technical parameters3.1 EA-D Special emergency power supply for fire emergency lighting
EPSS type backup emergency power supply
Project\Capacity |
10kVA |
15kVA |
20kVA |
30kVA |
40kVA |
50kVA |
60kVA |
80kVA |
90kVA |
100kVA |
|
Enter |
DC voltage |
360VDC or 492VDC |
|||||||||
Mains voltage |
380VAC (+15%, -20%) (default); in addition 380VAC±25% range can be set < /td> | ||||||||||
Mains frequency |
50HZ±5% (default), 50HZ±10% range can be set |
||||||||||
Two-way mutual investment |
Optional |
||||||||||
Output |
Output voltage |
Normal status: consistent with mains power |
|||||||||
Emergency status: 380 V±3% |
|||||||||||
Output frequency |
Normal status: consistent with mains power |
||||||||||
Emergency status: 50±0.1Hz |
|||||||||||
Number of output channels |
1 way (standard), another: 1-5 three-phase output optional |
||||||||||
Output method |
Continuous output (standard) |
||||||||||
Efficiency (rated load) |
≥98% (main power), ≥88% (emergency) |
||||||||||
Output waveform |
Sine wave |
||||||||||
Switching time |
≤4 ms, or ≤100 ms |
||||||||||
Overload capability |
120% long-term operation, 125% one-minute protection, 150% one-second protection |
||||||||||
Emergency power supply time |
90 minutes , also: can be customized according to user needs |
||||||||||
Protection function |
Over temperature protection, inverter over and under voltage protection, battery under voltage protection, overload protection, BUS over voltage, output short circuit protection |
||||||||||
Status display | LCD Chinese character information display+LED operation status indication |
||||||||||
Communication function |
RS485 (standard), another dry contact, LAN network port optional |
||||||||||
Control function |
Hand/auto function, forced start function, automatic monthly/annual inspection function, analog main power failure function, reset function, elimination |
||||||||||
Adapt to load |
Emergency lighting type lamp load |
||||||||||
Noise |
Normal state: ≤45dB |
||||||||||
Ambient temperature |
-10 degree-40 degree |
||||||||||
Relative humidity |
20%-90% |
||||||||||
Altitude |
≤1000m (for each additional 100 m power decrease 1%) |
||||||||||
Protection level |
IP41 |
||||||||||
Battery location |
Separate external battery cabinet |
Remarks: Specifications are subject to change without notice. The pictures are provided for reference, and the actual product shall prevail.