Dongguan Shengrong Communication Engineering Co., Ltd. Shengrong

UPS INDUSTRIAL POWER ONE-STOP SOURCE MANUFACTURER WHOLESALE

4dhcpmingchen

【Origin Pic】
Backup UPS power supply EA806 1kVA-30kVA
Power range:1kVA-30kVA
Application fields:Data processing center, computer room, IPS service 
★ 1. Basic introduction of EA800 series UPS

The second-generation EA800 series of intelligent chemical frequency UPS adopts the principle of online double conversion and uses DSP digital control technology to provide continuous, stable and pure sine wave power to the load. The whole system adopts full digital control, with high precision, high speed, simple control circuit and high reliability.

Power range

1kVA-30kVA

Application field:

Data processing center, computer room, IPS service provider, telecommunications, finance, securities, transportation, taxation, medical system, etc.

Has been certified by a third-party authority:

1kVA-10kVA single in and single out: Tyre certification, energy saving certification, radio and television certification

★ 2. Technical features of EA800 series UPS

1) Power supply method

1-10kVA single input single output; 10kVA above three input single output, support 380/400/415, 50/60Hz power grid system wide input voltage range and wide input frequency range, convenient for the access of fuel generators or other power generation equipment .

2) DSP full digital control

The second-generation EA800 series power converters and system components are all controlled by advanced DSP (digital signal processor), with high precision, high speed, simple control circuit and high reliability.

3) Super overload capability

(6-30kVA) When the load is less than or equal to 105%, work for a long time; when 105%

125%<load≤150%, switch to bypass output after 1 minute; when 150%<load≤200%, switch to bypass output after 200 milliseconds; 200%<load, switch to bypass output after 100 milliseconds;

4) Bypass dual DSP control design (no 1-3kVA), system reliability is further enhanced. 5) Redundant parallel machine (no 1-3kVA):

Using digital parallel technology, 6kVA (not including 6kVA) can support multiple parallel machines, and at the same time, parallel machines can share battery packs, reducing parallel costs.

6) Cold start and utility start function

If the utility power is abnormal, the UPS can be started directly with the battery to meet emergency needs. When there is no battery, the UPS can be started directly from the mains, which can be used as a high-precision stabilized power supply.

7) Super charging capacity (6-30kVA)

(1-3kVA):

1A/3A/6A (standard configuration)

(6-30kVA):

2A/4A/6A/8A/10A/12A adjustable (standard)

14A/16A/18A/20A/22A/24A adjustable (optional)

8) Friendly man-machine interface

Using large-screen LCD display and status indication, running status, operating procedures, data collection, fault detection materials and other content are clear at a glance.

9) Automatic frequency selection technology (LCD) 10) After the UPS is shut down, the battery can still be charged, extending battery life (6-30kVA) 11) Fault and alarm history records can be checked 12) Super network monitoring and management function

Standard RS232/USB communication interface.

13) Options: SNMP, dry contact, RS485

More options for 6-30kVA: parallel components, input isolation transformer, bypass isolation transformer, harmonic suppressor

★ 3. Technical parameters of EA200/300 series UPS

Type    number EA801 EA802 EA803 EA806 EA810 EA810(3/1) EA815(3/1) EA820(3/1) EA830(3/1)
Rated capacity 1kVA 2kVA 3kVA 6kVA 10kVA 10kVA 15kVA 20kVA 30kVA
Enter metrics
Enter the number of phases Single-phase three-wire (1Φ+N+PE) Three-phase five-wire (3Φ+N+PE)
Enter the rated voltage 220Vac/230Vac/240Vac 380Vac/400Vac/415Vac
Input voltage variable range 176-280Vac 165-275Vac 285-475Vac
Input frequency variation range 40-70Hz
Battery voltage 36VDC 72VDC 96VDC 192VDC
Number of battery cells Section 12V3 Section 12V6 Section 12V8 Section 12V16
output indicators
Number of output phases Single-phase three-wire (1Φ+N+PE)
Output rated voltage 220Vac/230Vac/240Vac
Output voltage regulation accuracy ±1%
Output frequency accuracy Mains mode: track bypass input in synchronization state; battery mode: 50Hz/60Hz±0.1Hz
Output power factor 0.8
Output waveform distortion degree Linear load≤3%, non-linear load≤6%
Output current crest factor 3:1
Inverter overload capacity When the load is ≤105%, work for a long time;
When 105%<load≤125%, switch to bypass output after 1 minute;
When 125%<load≤150%, turn to bypass output after 30 seconds;
150%<load, switch to bypass output after 500 milliseconds;
When the load is ≤105%, work for a long time;
105%<load≤125%, switch to bypass output after 10 minutes;
When 125%<load≤150%, switch to bypass output after 1 minute;
When 150%<load≤200%, transfer to bypass output after 200ms;
200%<load, switch to bypass output after 100 milliseconds;
Bypass overload capacity When 105%≤load<125%-20 minutes;
When 125%≤load<150%-2 minutes;
150% rated current≤load current--200ms;
When the load current is <150%, work for a long time;
150%≤load<200%-1 minute;
200% rated current≤load current--200ms;
System indicators
Switching time 0ms
Protection function Output short circuit, overload, output over-under-voltage, battery low-voltage, over-temperature protection, etc.
Communication interface Standard: RS232/USB  Optional: RS485/SNMP/dry contact
show    show LCD display
Work environment
Operating temperature 0~40℃
Storage temperature -25℃~55℃ (without battery)
Relative humidity 0%~95% (no condensation)
Altitude Altitude ≤1000m, over 1000m, derating 1% for every 100m rise
noise   sound <55dB (1 meter away from the device) <60dB (1 meter away from the device)
Other features
Host size         (W×D×H) mm 190×410×350 191×456×530 210×585×590 310×600×880 400×815×1100
Net  weight (kg) 18 33 40 54 96 130 201 230 277
yan   color black